Technical Policy And Procedure Notice #2/00

ISSUANCE #586


Date: 

July 24, 2000

Subject:

Semi-Controlled Inspection for Structural Light Gage Cold-Formed Steel, Plate Connected Wood Floor Trusses and Laminated Wood "I" Beams

Effective:

Immediately

Supersedes:

Brooklyn Borough Memorandum by Borough Superintendent George E. Berger dated August 11, 1983.

Background:

There have been several structural failures involving lightweight floor construction. Professional inspection is needed during construction of buildings and other structures utilizing it in order to insure that the delivered members are not damaged or defective, the installation is proper and safeguards are taken to prevent failure.

Purpose:

To set forth the requirements for the semi-controlled inspection of the construction, including size, quality, framing, erection and both temporary and permanent bracing of light gage cold-formed steel structural members, plate connected wood floor trusses and laminated wood "I" beams.

Reference:

Section 27-132(b) of the Administrative Code.

Specifics:

Requirements: The plans submitted for approval/ acceptance/professional certification showing these members shall be complete including member sizes, positions, locations, permanent and temporary bracing, fasteners (location, type and spacing), stiffeners, connections, etc., as needed for the proper erection of the structure.

The construction of all light gage cold-formed steel structural members, plate connected wood floor trusses and laminated wood "I" beams shall be subject to semi-controlled inspection for size, quality, framing, erection and both temporary and permanent bracing, as set forth below.

Size

Profiles used structurally shall conform to the specified dimension. Care shall be taken not to stretch, bend, or otherwise distort parts of the sections unless such forming is in the integral part of the design.

Quality

All materials shall be clean, straight, and undamaged. Damaged members shall be discarded. Only BSA/MEA approved laminated wood "I" beams shall be used. Glue shall completely bond all laminated wood "I" beam surfaces being joined. Quality Control for the erection of all members shall be under the supervision of the professional designated to perform the semi-controlled inspection.

Framing

Components may be cut by slitting, shearing, sawing, or flame cutting, as appropriate, in accordance with manufacturers' instructions and the design drawings. All punched holes and sheared or flame cut edges of material in members subject to calculated stress shall be clean and free from notches and burred edges. The approved/ accepted/professionally certified drawings shall be adhered to regarding member dimensions, locations, positions, beam separators, bearing surfaces and fasteners, including shear connectors, plate connectors, screws, bolts and welds, as applicable.

Erection

Care shall be taken to avoid damage to members when erecting, loading, unloading and otherwise handling them.

Bracing

Temporary bracing, shoring, jacks, etc. shall not be removed until the registered architect or professional engineer determines that they are no longer needed. Permanent bracing, web stiffeners, bridging, wind bracing, etc. shall be installed according to the approved/accepted/professionally certified drawings.

INSPECTIONS AND REPORT TO BE SUBMITTED:These inspections are to be performed by, or under the direct supervision of, licensed professional engineers or registered architects, who shall submit form(s) TR-1 indicating the following: "Semi-controlled inspection of light gage cold-formed steel structural members, plate connected wood floor trusses or laminated wood "I" beams (as applicable) per TPPN #2/00".